摘要

The liquid desiccant system can make a contribution to a sustainable path for maintaining healthy and comfortable indoor environments. The liquid desiccant system has two major subsystems, dehumidification and regeneration. Cold energy recovery was achieved by passing the indoor exhaust air through an air hose to import and dehumidify the inlet air prior to the precooling stage/phase. Heat energy recovery was effected by a heat exchanger. The system simply recycles the heat energy without any moisture transfer in the air, preheating the inlet air to the regeneration subsystem. Furthermore, based on the dehumidification capacity, regeneration capacity and the personal comfort criteria, the optimal match of air volume was selected. The results show the condition with the dehumidification airflow of 2600 CMH and the return air ratio in the range from 75% to 80% range was suitable for personal comfort. In this case, the matching regeneration airflow was 1600 CMH without heat recovery, so that the air flow rates for dehumidification and regeneration are optimal.

原文English
文章編號100826
期刊Thermal Science and Engineering Progress
22
DOIs
出版狀態Published - 1 5月 2021