跳至主導覽 跳至搜尋 跳過主要內容

Heat Transfer Performance of Microgroove Back Plate Heat Pipes with Working Fluid and Heating Power

  • Yanpeng Wu
  • , Jie Jia
  • , Dongmin Tian
  • , Yew Khoy Chuah

研究成果: 期刊貢獻文章同行評審

11 引文 斯高帕斯(Scopus)

摘要

Micro heat pipes (MHP) cooling is one of the most efficient solutions to radiate heat for high heat flux electronic components in data centers. It is necessary to improve heat transfer performance of microgroove back plate heat pipes. This paper discusses about influence on thermal resistance through experiments and numerical simulation with different working fluids, filling ratio and heat power. Thermal resistance of the CO2 filled heat pipe is 14.8% lower than the acetone filled heat pipe. In the meantime, at the best filling ratio of 40%, the CO2 filled heat pipe has the optimal heat transfer behavior with the smallest thermal resistance of 0.123 K/W. The thermal resistance continues to decline but the magnitude of decreases is going to be minor. In addition, this paper illustrates methods about how to enhance heat pipe performance from working fluids, filling ratio and heat power, which provides a theoretical basis for practical applications.

原文English
頁(從 - 到)982-991
頁數10
期刊Journal of Thermal Science
29
發行號4
DOIs
出版狀態Published - 1 8月 2020

文獻附註

Publisher Copyright:
© 2020, Science Press, Institute of Engineering Thermophysics, CAS and Springer-Verlag GmbH Germany, part of Springer Nature.

指紋

深入研究「Heat Transfer Performance of Microgroove Back Plate Heat Pipes with Working Fluid and Heating Power」主題。共同形成了獨特的指紋。

引用此